Citel Surge arrestor for data line DLU-24D3

Article Number: 14997
|
Network
|
4-20mA, Liaison 24V |
|
|
Nominal line voltage
|
Un |
24 V |
|
Max. DC operating voltage
|
Uc |
28 Vdc |
|
Cut-off frequency
-3dB, 100 ohm system
|
f max. |
> 140 MHz |
|
Cut-off frequency
-1dB, 100 ohm system
|
f max. |
> 60 MHz |
|
Insertion loss
|
< 1 dB |
|
|
Max. load current @25°C
|
IL |
300 mA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax |
20 kA |
|
Nominal discharge current
C2 Category
|
In |
5 kA |
|
Protection mode(s)
|
Common/Differential mode |
|
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
|
Up |
40 V |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
|
Up |
40 V |
|
Max. capacitance
|
C |
< 50 pF |
|
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp |
5 kA |
|
Line resistance (± 10%)
|
4.7 Ohm |
Geschatte verzendtijden: Nederland (2-3 werkdagen), EU (5 werkdagen), buiten de EU (1-2 weken).
Belangrijk: Zonnepanelen afrekenen is niet mogelijk via onze webshop . Neem contact met ons op via e-mail info@jedsenergy.com of bel naar +31649768077 . Speciale verzending is beschikbaar voor PV-modules.
Voor B2B-bestellingen bieden wij u graag een offerte met 0% BTW. Geef ons de benodigde details en wij zullen snel uw offerte op maat voorbereiden.
For B2B purchase, Please contact us for 0% VAT quote (ntra-Community deliveries of goods exempted from VAT ). Please provide your valid VAT Number and shipping address and then we'll send you customized quote. Please contact us by email info@jedsenergy.com or call at +31649768077.
Product datasheets and installation manuals are available for download on our webshop to assist you in making an informed decision.
Products returned due to incorrect selection, including compatibility issues, will not be accepted.